Free engineer-grade tool No signup required

Generator Sizing Calculator Sri Lanka.

Engineer-grade load calculation. Add your HVAC, pumps, lifts, lighting and process loads — get the right kVA, with starting-current analysis and tropical derating built in. Free, no signup, PDF output.

11 load categories Starting current method Tropical 40°C derating Branded PDF output

1Project & Building

Pick a building type to seed defaults. You can edit everything afterwards.

2HVAC — Air Conditioning

Split AC, VRF outdoor units, chillers, AHUs, FCU motors. Use the building heat-load calculator if you don't yet know the cooling capacity. Heat-load calculator →

DescriptionkWQtyStartingDiversity

3Pumps & Motors

Water transfer, booster, fire (jockey + main), sewage, HVAC chilled-water and condenser pumps, cooling-tower fans. Starting type matters: Direct-on-Line motors draw 6× their rated current at start.

DescriptionkWQtyStartingDiversity

4Lifts & Vertical Transport

Passenger lifts, service lifts, escalators, dumb-waiters. Modern VVVF lifts are gentler on starting current than older AC two-speed.

DescriptionkWQtyStartingDiversity

5Lighting & General Power Outlets

Add total lighting and socket-outlet load. As a guide: offices ~12 W/m² lighting, hotels ~15 W/m², factories ~10 W/m². Sockets typically diversify to 30-50%.

DescriptionkWQtyStartingDiversity

6Kitchen Equipment

Hotels, hospitals, restaurants. Combi ovens, walk-in coolers, induction hobs, dishwashers, exhaust fans. Diversity is high in commercial kitchens — typically 40-60% running simultaneously at peak.

DescriptionkWQtyStartingDiversity

7Laundry Equipment

Industrial washers, dryers, irons, calenders, finishers. Hotels and hospitals only. Dryers are heavy continuous loads; washers have brief inrush.

DescriptionkWQtyStartingDiversity

8Medical Equipment

Hospital backup loads — OT lights, ICU, ventilators, MRI, CT, X-ray, dialysis, autoclaves, lab refrigeration. Critical loads must always be 100% backed up.

DescriptionkWQtyStartingDiversity

9Industrial / Process Machinery

Factory motors, compressors, conveyors, mixers, presses, CNC machines. Use VFD wherever possible — cuts starting current to ~1.2×.

DescriptionkWQtyStartingDiversity

10IT & UPS Systems

UPS systems, server rooms, data halls. UPS adds an inrush surge on start (~4× rated kVA briefly). For data centres, consider 2N redundancy.

DescriptionkWQtyStartingDiversity

11EV Chargers

Increasingly common for hotels and offices. AC chargers (7-22 kW) are continuous loads; DC fast chargers (50-150 kW) need careful generator sizing.

DescriptionkWQtyStartingDiversity

12Other Loads

Anything else — pool pumps, garden lighting, fountains, signage, water features, future expansion allowance.

DescriptionkWQtyStartingDiversity
Engineering disclaimer. This calculator gives a sized indication based on standard Sri Lankan industry practice (CIBSE / IEC / NFPA reference, 40°C ambient, 0.8 PF, 20% margin). Final selection must be reviewed by a qualified electrical engineer who has visited the site and inspected the actual load profile, single-line diagram and starting sequence. NativeWay's engineers will validate this calculation as part of any quotation.

Why starting current matters

A motor at start draws 4–7× its rated current. The genset must handle this surge without voltage drop greater than 15%, or the motor stalls.

Why tropical derating

Sri Lankan ambient is 35°C; gensets are rated at 25°C ISO. Derate ~5% for cooling efficiency loss in tropical conditions.

Why diversity factor

Not every load runs simultaneously. Hotels run ~70% of HVAC at peak; factories run ~80% of motors. Apply realistic diversity per category.

Beyond this calculator

Final sizing should account for harmonics, future expansion, parallel operation needs, and the actual single-line diagram. Talk to our power engineers.